氣動切斷閥安裝后的線路調試 |
發布者: 點擊:911 |
(1)氣(qi)動切(qie)斷閥(fa)(fa)(fa)輸(shu)(shu)入信(xin)號(hao)(hao)的(de)連接:通常,與閥(fa)(fa)(fa)門定位器(qi)一(yi)(yi)起檢查。控(kong)制(zhi)閥(fa)(fa)(fa)輸(shu)(shu)入信(xin)號(hao)(hao)來自(zi)控(kong)制(zhi)器(qi),因此(ci),從控(kong)制(zhi)器(qi)輸(shu)(shu)出(chu)一(yi)(yi)個(ge)(ge)起點(dian)信(xin)號(hao)(hao),檢查控(kong)制(zhi)閥(fa)(fa)(fa)是(shi)(shi)否在起點(dian)位置;輸(shu)(shu)出(chu)一(yi)(yi)個(ge)(ge)終點(dian)信(xin)號(hao)(hao),檢查控(kong)制(zhi)閥(fa)(fa)(fa)是(shi)(shi)否在終點(dian)位置。為(wei)此(ci),應(ying)檢查供(gong)(gong)(gong)氣(qi)氣(qi)源壓(ya)力(li)是(shi)(shi)否正常;過濾減壓(ya)器(qi)工(gong)作是(shi)(shi)否正常;液壓(ya)系統供(gong)(gong)(gong)給的(de)油(you)壓(ya)是(shi)(shi)否正常;供(gong)(gong)(gong)電是(shi)(shi)否正常;輸(shu)(shu)出(chu)信(xin)號(hao)(hao)是(shi)(shi)否正確等。并在測量范圍內至少取5點(dian)檢查輸(shu)(shu)入信(xin)號(hao)(hao)與閥(fa)(fa)(fa)位之間是(shi)(shi)否滿足(zu)所需關(guan)系。應(ying)檢查氣(qi)開、氣(qi)關(guan)的(de)作用方式(shi)是(shi)(shi)否正確,是(shi)(shi)否滿足(zu)工(gong)藝(yi)生(sheng)產(chan)過程的(de)安全生(sheng)產(chan)要求。 (2)氣動切斷閥(fa)輸(shu)出信號(hao)(hao)的連(lian)接(jie):控(kong)制(zhi)(zhi)閥(fa)輸(shu)出信號(hao)(hao)是(shi)閥(fa)位(wei)信號(hao)(hao),可以是(shi)模擬量(liang)(liang)信號(hao)(hao)或數(shu)字量(liang)(liang)信號(hao)(hao)。應(ying)(ying)在檢(jian)查(cha)控(kong)制(zhi)(zhi)閥(fa)輸(shu)入(ru)信號(hao)(hao)的同時,檢(jian)查(cha)閥(fa)位(wei)信號(hao)(hao)是(shi)否(fou)正確(que)。采用HART或智(zhi)能電氣閥(fa)門定(ding)位(wei)器時,應(ying)(ying)檢(jian)查(cha)閥(fa)位(wei)狀態信息(xi)能否(fou)正確(que)傳(chuan)輸(shu)。控(kong)制(zhi)(zhi)閥(fa)全行(xing)程運行(xing)過程中應(ying)(ying)偵聽(ting)控(kong)制(zhi)(zhi)閥(fa)閥(fa)芯和閥(fa)座是(shi)否(fou)有機械振動和異常雜聲。 (3)手輪機(ji)(ji)構(gou)(gou)調試:檢查手輪機(ji)(ji)構(gou)(gou)能否(fou)正確轉動和動作,限位和鎖定(ding)裝置是否(fou)好用。 (4)當出現偏(pian)差超過允許偏(pian)差限時(shi),應進行相應的調試。例如,改(gai)變(bian)閥(fa)位開關的位置,檢查接線(xian)或管路是(shi)否有泄(xie)漏等 |
相關新聞: 氣動切斷閥的工作原理以及主要功能 角座控制閥的原理與優勢特點 角座控制閥的工作原理與優勢特性 氣動切斷閥的施工注意事項 角座控制閥的構造優勢特性 |
![]() ![]() |